Jci Metasys Software Ads Documentation Download Updated FREE

Jci Metasys Software Ads Documentation Download

Manufacturer

Johnson Controls

Model

MW-MTOOL-0

Description

M-Tools
This is the consummate Thousand-Tool Package for a new installation.

  • Includes HVAC Pro configuring and commissioning utilities for the UNT, AHU, VAV, and VMA Metasys N2 Open devices.

  • Includes GX-9100 configuring and commissioning utilities for the DX-9100

  • Includes many other utilities

Note: This software volition not run on a 64-bit OS.
Note: Supports COM1 and COM2 only

How do I request support for an integration to Schneider Electric SBO?

All S4 partners are required to provide pre-sales technology back up and 1st level technical support to their dealers and integrators. For Schneider Electrical dealers and branches the all-time way to asking this support is to e-mail the problem or assistance request details into the Production Back up (PSS) queue direct:

product.support@schneider-electric.com

Alternatively, there are different dial-in numbers people can use to log a new case (one for each of the three dissimilar cities where PSS is located).

Emailing this address (or calling in and dictating your instance details to the person manning the phone) starts the process. PSS will facilitate any necessary escalation within the Schneider Electrical support organizations or to The S4 Group.

What do I expect for if there are legacy N2 Jitney Problems?

If there has been a history of devices going off line in the pure Metasys environs it is a sign that something is wrong.

  • It could exist bad wiring,

  • it could be too many N2 devices on the bus,

  • it could be EMF,

  • it could be a bad transmitter on a N2 device,

  • it could exist multiple masters accidentally installed on the motorbus.

Make up one's mind the issue and correct it earlier proceeding with the integration.

Are Metasys Generic IO / Point Multiplexor applications Supported?

Yep. However, it takes more work than for the awarding specific controller applications. Consider the existence of Signal Multiplexor applications a Yellowish flag when preparing for an integration. It says that there is probably a lot of logic in the NCM driving the points in these devices.

The normal designed operation of the Metasys N2 DDC controllers is that if they lose communication with their supervisory controller (NCM, Facilitator, Companion, N30, NAE, Facility Explorer) they volition go along operating the building utilizing the terminal bachelor values or default values for all parameters, etc. For instance, Outside Air Temperature is typically a global variable that is distributed by the supervisory controller to all N2 devices that demand the information. If the supervisory controlle fails, or communications to it via the N2 bus are lost, the individual controllers will continue operating with the best information they that have available.

If N2 devices are ...

How practice I tune the N2 Coach for maximum performance?

We've seen multiple areas where improvements can be made in existing N2 buses. From an electric point of view the N2 motorcoach follows the RS-485 standard with a N2+, N2-, and reference line. In many cases we will point you back to JCI documentation for details. Nosotros're not going to try to re-engineer the N2 bus engineering science. It is what information technology is.

We have seen many cases where either improper installations or just normal wear and tear over the years has taken its toll. Information technology'southward as well a fact that once you integrate to a legacy N2 autobus with either the OPC-N2 Router or the BACnet-N2 Router information technology volition be driven harder than it has ever been driven before. If annihilation is marginal, information technology volition exist exposed by the additional load put onto the system.

Nosotros always advise our integration partners to validate the N2 motorbus every bit role of determining the scope of an integration project. In fact, we suggest them to specify in their contract that the client deliver to them an in-spec and working N2 passenger vehicle with wo...

How practice I prepare for a N2 autobus Integration?

The more information you have at manus the less risky a N2 integration will be and the more successful the project will be. In preparation for a N2 integration nosotros always recommend that you:

  • Use HVAC Pro and create a Network Map report with it. This volition tell you the hardware type, Firmware versions, and application loaded into each N2 device.

  • If y'all run into any Generic IO / Bespeak Multiplexor applications this is a ruby flag. That means that the logic driving those points is back in an NCM, or other supervisory controller. You can still exercise a very successful integration. You merely demand to practise more planning.

  • Brand certain that each N2 motorbus segment is within electrical specifications. You can use the ComBus Quick Tester or a DVM. You will be driving the N2 passenger vehicle harder than it has ever been driven before so whatever weakness will come out.

  • Review as built drawings and any other documentation that is available for the Metasys installation. I've taken the approach of s...

Practice S4 Open Appliances support Programming Configuring and Commissioning N2 Devices?

When we designed the S4 Open Appliances we determined that we would terminate short of providing these services. Johnson Controls has very effective tools for performing these functions that are aware of all of the variations in firmware, awarding revisions, etc. Nosotros didn't experience that we could add together whatsoever value in this area.

Apply HVAC Pro for N2 Open devices like the UNT, VAV, and AHU

Utilise HVAC Pro for the VMA

Use GX-9100 for the DX-9100

1 of the things that we did include in the design is the ability to easily determine the application loaded into N2 devices, the firmware version running in the device, the original configuration file name, etc. This information is provided on the properties folio for each device in the Edifice Control Network, BCN, folder. The information provided by each device type varies. Details for many N2 devices are provided at present. Others will be added in the future every bit time and resources allow.

How are S4 Open Device Type Templates different from Metasys Configuration Files?

We developed the concept of Device Type Templates so that we would non have to rely on Metasys configuration files being either available, or upwardly to date. They also expose more points than Metasys typically would. For instance PID loop tuning parameters and other parameters that would commonly but be exposed by the Metasys configuration utilities are exposed so that 3rd political party tuning and continuous commissioning applications can be utilized for a Metasys system.

As background, here'southward the process that nosotros use in the Configure wizard to try to notice the best friction match with indicate mapping. N2 devices are interrogated to make up one's mind their hardware blazon and the application loaded into them.

one) All-time case – nosotros have a Device Type Template that matches both the hardware type and the application loaded into device. Nosotros refer to these every bit Application Specific Device Type Templates.

two) Next best – we friction match on the hardware blazon but non the application. We assign a generic indicate map ...

Can I integrate to N2 VMA Devices?

The VAV Modular Associates, VMA, was ane of the last device families to receive support in the S4 Open up Appliances. These devices utilize their own variation of the N2 protocol referred to equally N2B. With this work completed we support all variations of the N2 protocol and any N2 device that could be found on a N2 motorbus.

Why is my OPC client returning all 0 values for points on some N2 devices?

The OPC server associated with the S4 Open up: OPC-N2 Router provides a Quality ;aspect for each point that information technology publishes. This indicates if the S4 Open Appliance is successfully talking to the field devices and retreiving data points. Unfortunately, some OPC clients ignore the Quality indicator and instead default the information values to zero.

The S4 Open Apparatus will retry transactions to a N2 device multiple times earlier it gives up and returns a BAD Quality indication.

Another symptom of this same problem is that the Configure Sorcerer fails to find all of the N2 devices on the omnibus. If the Configure Wizard does not find a device that you lot know is on the N2 bus that tells us that there was interference during the time that nosotros were trying to access N2 address XX (in hex). It is not necessarily a trouble with the device at this address. The Wizard simply saw the bad manual in the time frame that we were expecting a response from this device.
...

How practise I add new N2 devices to an already deployed router?

  1. Create the device in the physical network in which it resides (network north -> new -> field device)
  2. The "Define Concrete Device" window will open; assign the N2 address for this device
  3. The device should at present announced under the correct N2 network
  4. Now create a device object in the Building Control Network. Specify the N2 address that yous want the device published to in the Upstream N2 network. (BCN -> New -> Device...)
  5. Link this object to the Physical Field Device you created in the physical network
  6. Assign the appropriate device type template for this device 
  7. The device is now integrated into the organisation and can be discovered by your BACnet customer

How do I connect M-Tools (HVAC Pro and GX9100) to the N2 omnibus?

The Metasys N2 bus follows the RS-485 standard for its physical and electrical characteristics. Information technology runs at 9600 BD, half duplex using N2+, N2-, and Ref wires. Our S4 Open appliances are pre-configured to have all Com ports operate in RS-485 style.

If y'all run whatever of the JCI Metasys configuration or commissioning tools HVAC Pro, GX-9100, etc. from your labtop or another Windows PC and desire them to communicate the the N2 bus via their COM port yous'll accept to utilize either a USB to RS-485 or a RS-232 to RS-485 converter.

We have been using RS-485 converters from B&B Electronics www.bb-elec.com to connect our PCs to the N2 bus.

For RS-232 to RS-485 we use their model 485SD9TB

For USB to RS-485 (N2 bus) we utilize their model number 485USBTB-2W

The USB Serial Port technology has go so standardized that most manufacturers' products should work fine although the B&B products are the only ones we have tested. Notation that y'all may accept to a...

Tin can I make the JCI Metasys N2 double-decker run faster?

The JCI design of the N2 bus is stock-still at 9600 Bd. We have to live with that. It can't be changed.

And so, the problem becomes how do nosotros adapt BACnet IP or OPC transactions coming in at Ethernet speeds?

  • Transparent Caching and BACnet COV support improve efficiency

  • Validating the N2 charabanc, repairing any installation problems, and removing sources of electrical interference better functioning

  • Breaking the N2 bus into smaller segments distributes the load. Each segment may come up into a separate Downstream N2 Interface on a N2 Router or each one come up into a separate N2 Router

  • Poll rates may need to exist adjusted to frequencies more realistic for the capabilities of the N2 motorcoach

How do I work with Generic IO / Indicate Multiplexor Metasys applications?

Every bit our integration partners have been digging into some of the older Metasys® installations they are finding Generic IO / Betoken Multiplexor applications much more oftentimes than I thought they would.

Y'all tin can still do a very successful integration with these devices simply it may take a bit more than planning than if they were loaded with more than traditional Metasys® applications.

  • Yous can process the .PRN Metasys configuration (resource) file for these devices through the S4 Configuration File Conversion Utility to create a custom device template

  • You may need to investigate custom logic in the Metasys supervisory controller. For the NCM this would be GPL or JC Basic logic.

  • You may be able to determine how the points are used by investigating the assignment and presentation of points in the Metasys Operator Workstation

  • You can investigate Single Side Loop logic, Interlocks, etc. programmed into the N2 device itself utilizing HVAC Pro

How do I set Occupied / Unoccupied schedules for N2 devices with the S4 Open up appliance?

Most N2 devices do non contain a time of solar day clock that you tin can admission directly. They do have an on-board clock that can be synchronized with the caput finish and is used as a fallback when the N2 device becomes disconncted from the head finish. In normal operation they completely rely on a supervisory controller to tell them if they should exist in Occupied or UnOccupied manner by toggling a binary point.

Typically, you'll see gear up points for Occupied fashion and some other pair for UnOccupied mode. But have your new HMI or some other (BACnet or OPC equally appropriate) controller toggle the Occupied point in each N2 device to indicate the mode that you lot want each controller to operate in.

Check the manufacturer documentation for each N2 device and awarding supported by information technology for the correct point to toggle the Occupied / UnOccupied condition of the device and the point names assigned for the setpoints.

Where can the HVAC Pro or GX-9100 utilities be purchased?

One of the most of import aspects of a successful Metasys integration is in taking the time to empathise the existing N2 devices and their configurations.

  • HVAC Pro is the Metasys configuration and commissioning utility used for N2 Open devices like Unitary Controllers (UNT), AHU, and VAV controllers. It is also used for the VAV Modular Associates (VMA) devices.

  • GX9100 is utilized to program and commission the DX-9100 device.

These utilities are available as role of the M-Tools parcel through authorized Metasys distributors. At that place are frequent discussions about acquiring, installing, and working with these utilities on the HVAC Talk forum, http://www.hvac-talk.com.

You tin also purchase the M-Tools package through The S4 Grouping.

Phone call united states of america and we'll help you find the right solution. M-F 11am-7pm Eastern

Let united states of america know what yous are looking for past filling out the grade below.

Order Inquiry Course

Documentation

Installation and Performance (PDF)

12.01.2016

User Guide for the S4 Open up Appliances

Configuration File Conversion Utility (PDF)

12.01.2016

S4 utility that converts Metasys configuration (Resource) files to templates for the S4 Open up Appliances

Presentation

Technical Presentation (PowerPoint)

12.01.2016

S4 Open Appliances Technical Presentation

Jci Metasys Software Ads Documentation Download